Circuit Breaker Input for Time-Trip Specific OEM Applications with Grounded Neutral

Continually senses for residual ground fault currents and provides solid-state SCR output for circuit breaker when fault current exceeds setpoint. When applied with appropriate circuit breaking devices, the RGCS serves as the sensing component of a GFCI system.

Theatrical, Carnival and Entertainment Industry

Applied on electrified equipment regularly in close proximity to personnel, such as those on stage and movie sets, RGCS senses leakage currents and signals when cumulative ground currents surpass safe levels. Can be coupled to alarm indicators or circuit interruption devices.

Portable Power Generation and Distribution

Enables end-users to detect or monitor leakage current in branch circuits, triggering a breaker to interrupt power in faulty branch without having to disconnect the main.

Industrial, Pool, Spa, and Fountain Applications

Monitors ground current for pool, spa, fountain and other industrial equipment located in the vicinity of water or damp conditions. Provides ground fault detection and output to circuit breaker for GFCI applications.

Features

15 mS Sensor Response Time

Exceeds response times specified by UL 943, allows

more time for the circuit breaker to meet required

time-trip performance.

Factory Calibrated Trip Point

Setpoint is factory adjusted from 6mA to 30mA,

ensuring proper setpoint operation up to UL 943

Class A or B performance standards. Factory calibration

eliminates potential for undesired field modifications.

Industrial Grade Performance

0-100A input range offers application flexibility for use

on industrial systems or larger installations. Sensors offer

constant hysteresis and linear response characteristic

for enhanced accuracy to setpoint. Integral "Zero-Sum"

CT allows for quick and easy one-piece installation.

Industrial Grade Performance

Constant hysteresis and linear response characteristic

enhance accuracy to setpoint.

Specifications

Dimensions

Power Supply 120VAC or 240VAC

Output Solid State AC Switch; Isolated Dry Contact

Output Rating 1A@240VAC

Trip Point Range 6 - 30 mA, Factory Set

Response Time 15-25 ms

Tolerance +/- 1%

Input Range 0-100A

Offstate Leakage None

Hysteresis 5% (Constant)

Isolation Voltage 1,250 VAC

Frequency Range 60 Hz

Case UL 94 V-O Flammability Rated

Environmental-4 to 122°F (–20 to 50°C), 0-95% RH, non-condensing

Sensing Aperture 0.75" (19.1mm) diameter

Agency Approvals* Must be submitted for UL 943 approval with appropriate customer-supplied circuit breaker.  RGCS Sensors are intended to serve as a

component of a GFCI system and, as such, are not UL approved. Please consult with factory.

Ordering Information

Example: RGCS-NOR-120-FAT-010

Residual ground current sensor with 10mA setpoint, N.O. 1A@240VAC output, 120VAC supply, fast-acting trip response for use with circuit breaker, solid-core enclosure.